(Ctrl+Click if PDF doesn't appear)
Construction
| Diameters (In) |
1) Component 1 | 2 X 1 COND | |
a) Conductor | 22 (7/30) AWG BC | 0.029 |
b) Insulation | 0.0365" Wall, Nom. Foam HDPE | 0.102 |
(1) Color(s) | | |
Cond | Color | Cond | Color | Cond | Color | 1 | RED | 2 | GREEN | | |
|
2) Cable Assembly | 2 Components Cabled | |
a) Twists: | 4.8 Twists/foot (min) | |
3) Shield: | Alum/Mylar Tape, 25% Overlap, Min. | |
a) Foil Direction | Foil Facing Out | |
b) Braid | TC,65% Coverage, Min. | |
4) Jacket | 0.042" Wall, Nom.,PVC | 0.315 (0.325 Max.) |
a) Color(s) | VIOLET |
b) Print | ALPHA WIRE P/N 6463 PROFIBUS CABLE 1PR22 SHIELDED PVC (UL) CMG EXXXXX OR PLTC OR C(UL) CMG SUN RES CE ROHS (SEQ FOOTAGE EVERY 2FT) [Note: Product may have c(UL) or CSA markings depending upon plant of manufacture.] |
Applicable Specifications
1) UL | CMG | 75°C |
| SUN RES | |
| PLTC | 75°C |
2) CSA International | CMG | 75°C |
3) CE: | EU Low Voltage Directive 2006/95/EC |
Environmental
1) CE: EU Directive 2011/65/EU(RoHS2): |
| This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011. No Exemptions are required for RoHS Compliance on this item. Consult Alpha Wire's web site for RoHS C of C. |
2) REACH Regulation (EC 1907/2006): |
| This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration. |
Properties
Physical & Mechanical Properties |
---|
1) Temperature Range | -30 to 75°C |
2) Bend Radius | 10X Cable Diameter |
3) Pull Tension | 14 Lbs, Maximum |
Electrical Properties | (For Engineering purposes only) |
---|
1) Voltage Rating | 300 VRMS |
2) Characteristic Impedance | 150 Ω +/- 15
|
3) Mutual Capacitance | 8.5 pf/ft @1 kHz, Nominal
|
4) Ground Capacitance | 27.9 pf/ft @1 kHz, Nominal
|
5) Velocity of Propagation | 78 %
|
6) Conductor DCR | 16 Ω/1000ft @20°C, Nominal
|
7) OA Shield DCR | 3.9 Ω/1000ft @20°C, Nominal
|
8) Current | 2.3 amps per conductor @30°C, Maximum
|
9) Attenuation, Max dB/100ft | 0.34 @ 200 kHz
|
| 0.81 @ 4 MHz
|
| 1.64 @ 16 MHz
|
Other
Packaging | Flange x Traverse x Barrel (inches) |
a) 1000 FT | 18 x 12 x 8 Continuous length |
b) 500 FT | 12 x 10 x 5 Continuous length |
c) 100 FT | 12 x 4.5 x 3.5 Continuous length |
| [Spool dimensions may vary slightly] |
Notes: |
a) PROFIBUS DP Cable |
Alpha Essentials Data & Bus Cable:
Offering industry-leading mechanical and electrical performance for the major industrial automation protocols, including ControlNet™, RS-485, DeviceNet™, Fieldbus, PROFIBUS™, and Industrial Twinax. With multiple configurations, we are sure to meet the needs of your demanding applications.
ControlNet™ Cable
- Low-loss RG-6/U 75-ohm coaxial cable
- Double braid/foil shielding for maximum signal integrity and run length
RS-485 Cable
- 1 to 4 pairs
- Braid/foil shield to reduce electrical noise sensitivity
- UL Type PLTC Open Wiring (300 V)
- Sunlight resistant
DeviceNet™ Cable
- Power and data in a rugged two-pair cable
- Sunlight resistant
- Available for ODVA thick and thin trunks
- Compliant with Allen-Bradley part numbers 1485 CPI-A and 1485 CPI-C
Fieldbus and PROFIBUS™ Cable
- 100-ohm impedance for Types A and B Fieldbus
- 150-ohm impedance for High-Speed Fieldbus and PROFIBUS DP
Industrial Twinax Cable
- Meets the requirements of Allen-Bradley Data Highway Networks
Request a Sample
Download Brochure
Consult a Cable Expert
Need a more unique construction? Different color code? Different color Jacket?
Request a Custom Quote
Resources