Construction
| Diameters (In) |
1) Component 1 | 4 X 1 COND | |
a) Conductor | 8 (133(7x19)/29) AWG TC | 0.166 |
b) Insulation | 0.061" Wall, Nom. XLPE | 0.288 |
(1) Color(s) | | |
Cond | Color | Cond | Color | Cond | Color | 1 | BLACK#1 | 3 | BLACK#3 | | | 2 | BLACK#2 | 4 | GREEN OR GREEN/YELLOW | | |
|
2) Cable Assembly | 4 Components Cabled | |
a) Twists: | 1.1 Twists/foot (min) | |
3) Shield: | A/P/A Tape, 25% Overlap, Min. | |
a) Drain Wire | 4 x 14 (41/30) AWG TC | |
b) Braid | TC,85% Coverage, Min. | |
4) Jacket | 0.086" Wall, Nom.,TPE | 0.920+/- 0.020 |
a) Color(s) | BLACK |
b) Jacket Separator | Tissue Tape, 25% Overlap, Min. | |
c) Print | ALPHA WIRE-L VF16008 VFD CABLE 4C8 SHIELDED (UL) 1000V FLEXIBLE MOTOR SUPPLY CABLE 600V TYPE TC-ER -40C RHW-2 CDRS XLPE/TPE 90C DRY/WET SUN RES OIL I/II OR 8 AWG C(UL) CIC CONTROL/TC -40C SUN RES 90C WET/DRY XLPE INS FT4 CE ROHS (DATE CODE) (SEQ FOOTAGE) [Note: Product may have c(UL) or CSA markings depending upon plant of manufacture.] |
Applicable Specifications
1) UL | | |
a) Component 1 | RHW-2Wet/Dry | 90°C Dry / 90°C Wet / 600 VRMS |
| XHHW-2Wet/Dry | 90°C Dry / 90°C Wet / 600 VRMS |
b) Overall | TC | 90°C / 600 VRMS |
| EXPOSED RUN | |
| SUN RES | |
| 1000V Flexible Motor Supply Cable | |
| OIL RES I/II | |
2) CSA International | C(UL) -40C | |
| C(UL) CIC CONTROL | |
| C(UL) TC | |
| C(UL) FT4 | |
3) CE: | EU Low Voltage Directive 2006/95/EC |
Environmental
1) EU Directive 2002/95/EC(RoHS): |
| All materials used in the manufacture of this part are in compliance with EU Directive 2002/95/EU regarding the restriction of use of certain hazardous substances in electrical and electronic equipment. Consult Alpha Wire's web site for compliance Date of Manufacture. |
2) REACH Regulation (EC 1907/2006): |
| This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration. |
3) California Proposition 65: | The outer surface materials used in the manufacture of this part meet the requirements of California Proposition 65. |
Properties
Physical & Mechanical Properties |
---|
1) Temperature Range | -40 to 90°C |
2) Bend Radius | 10X Cable Diameter |
3) Pull Tension | 689 Lbs, Maximum |
4) Sunlight Resistance | Yes |
5) Copper Weight | 338 Lbs/1000Ft |
Electrical Properties | (For Engineering purposes only) |
---|
1) Voltage Rating | 1000 VRMS |
2) Characteristic Impedance | 62 Ω
|
3) Inductance | 0.181 µH/ft, Nominal
|
4) Mutual Capacitance | 30 pf/ft @1 kHz, Nominal
|
5) Ground Capacitance | 62 pf/ft @1 kHz, Nominal
|
6) Conductor DCR | 0.68 Ω/1000ft @20°C, Nominal
|
7) OA Shield DCR | 0.4 Ω/1000ft @20°C, Nominal
|
8) Current | 44 amps per conductor @30°C, Maximum
|
9) Insulation Resistance | 300 MΩ/MFt (Est.)
|
Other
Packaging | Flange x Traverse x Barrel (inches) |
a) Bulk(Made-to-order) | |
Industrial Series V-Flex (Flexible VFD):
Alpha Wire's Series V-Flex Flexible VFD Cable is specifically designed to combat the problems of system performance and signal disruption. When generic cables degrade over time, V-Flex keeps VFD systems running with required precision. With new levels of flexibility, it makes routing and installation fast and easy.
Series V-Flex Features:
- Rated for use at temperatures as low as -40°C
- UL and CSA Tray Cable approved
- Sunlight resistance and excellent resistance to solvents and oils
- TPE jacket
- 5x Static Bend Radius
Series V-Flex Benefits:
- Superior flexibility for easier routing and easier handling
- Reduced chance of cable failure from voltage irregularites such as harmonics, corona discharges, and power distortion
- Low capacitance for improved signal transmission
- Double shielded for maximum EMI protection
Request a Sample