Pro Met 470027YY
Pro Met 470027YY
Pro-Met industrial cables are designed to perform better, providing consistent and reliable operation. The result is more uptime, fewer errors, and precise operation of equipment. Pro-Met’s round construction makes it easier to install, seal, and route.
Construction
Diameters (mm) | ||||||||||||||
1) Component 1 | 2 X 1 COND | |||||||||||||
a) Conductor | 0.75 (30/.177) mm2 Bare Copper | 1.11 | ||||||||||||
b) Insulation | 0.400 mm Wall, Nom. PVC | 1.91+/- 0.08 | ||||||||||||
(1) Print Color |
WHITE |
|||||||||||||
(2) Color Code | Alpha Wire Color Code KZ | |||||||||||||
|
||||||||||||||
2) Cable Assembly | 2 Components Cabled | |||||||||||||
a) Twists: | 13.1 Twists/meter (min) | |||||||||||||
b) Orientation: | Components to be arranged from INSIDE LAYER to OUTSIDE LAYER | |||||||||||||
3) Jacket | 0.66 mm Wall, Nom.,PVC | 5.23 (5.43 Max.) |
||||||||||||
a) Color(s) | GREY | |||||||||||||
b) Print | ALPHA WIRE-* P/N 470027YY PRO-MET 300/500V 2X0.75MM2 PVC/PVC MULTI CORE CONTROL CABLE ◁ VDE-REG 8770 ▷ CE ROHS DDDYANN XXXXXXX M * = Factory Code |
Applicable Specifications
1) IEC | ||
a) Component 1 | EN 60228 Conductors, Class 5 | |
DIN VDE 0295 Class 5 |
||
2) Other | IEC 60332-1 Flame Behavior | |
DIN EN 50290-2-22 Oil Resistance |
||
UV Resistant | ||
3) CE: | EU Low Voltage Directive 2014/35/EU |
Environmental
1) CE: EU Directive 2011/65/EU(RoHS2): | ||
This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011and the amending Directive 2015/863/EU of 4 June 2015 . No Exemptions are required for RoHS Compliance on this item. Consult Alpha Wire's web site for RoHS C of C. | ||
2) REACH Regulation (EC 1907/2006): | ||
This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration. |
Properties
Physical & Mechanical Properties | |
---|---|
1) Temperature Range | -40 to 80°C(static), -30 to 70°C (dynamic) |
2) Bend Radius | 4X Cable Diameter(static), 10X Cable Diameter(dynamic) |
3) Sunlight Resistance | Yes |
Electrical Properties | (For Engineering purposes only) |
1) Voltage Rating | 300/500 VRMS |
2) Conductor DCR | 26 Ω/Km @20°C, Max. |
Other
Packaging | Flange x Traverse x Barrel (inches) |
a) 300 M | 12 x 10 x 5 Continuous length |
b) 100 M | 12 x 4.5 x 3.5 Continuous length |
c) 50 M | 12 x 4.5 x 3.5 Continuous length |