Part # AWG  Stranding  Construction Type  # of Elements  Shielding  Jacket Diameter  Temperature Range  Voltage  Applicable Specifications 
80014 22  19/34  COND  UNSHIELDED  0.172  -50 to 90  600  CA Prop 65, CE, CSA AWM I/II A/B, CSA FT2, IEC 60332-1, IEC 60332-2, IEC 60754-1, IEC 60754-2, IEC EN 60228 Conductors, Class 6, REACH Regulation (EC 1907/2006), ROHS - RoHS Compliance, UL 60C OIL, UL AWM 21959, UL SUN RES 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 2 X 1 COND 
a) Conductor 22 (19/34) AWG Tinned Copper 0.032
b) Insulation 0.010" Wall, Nom. MPPE 0.052
(1) Print ALPHANUMERIC NUMBERS - 1-ONE ALTERNATING AND
INVERTED
(2) Color Code Alpha Wire Color Code KX
Cond Color Cond Color Cond Color
1 GREEN/YELLOW 2 BLACK#1 
2) Cable Assembly 2 Components Cabled 
a) Twists: 12.0 Twists/foot (min) 
b) Orientation: Components to be arranged from INSIDE LAYER to OUTSIDE LAYER 
c) Core Wrap Nonwoven Polyester Tape, 25% Overlap, Min. 
3) Jacket 0.032" Wall, Nom.,Polyurethane, Zero Halogen (ZH)0.172+/- 0.010
a) Color(s) SLATE
b) Print ALPHA WIRE-* P/N 80014 2C 22 AWG
RU AWM STYLE 21959 90C 600V SUN RES 60C OIL OR
CRU AWM I/II A/B 90C 600V FT2 --- IEC EN 60332-1/2
CE ROHS (SEQ FOOTAGE)
* = Factory Code
1) UL   
a) Component 1 AWM/STYLE 11231 105°C / 600 VRMS
b) Overall AWM/STYLE 21959 90°C / 600 VRMS
 60C OIL 
 SUN RES 
2) CSA International C(RU) AWM I/II A/B 90°C / 600 VRMS
 FT2 
3) IEC   
a) Component 1 EN 60228 Conductors, Class 6 
b) Overall EN 60754-1 Acid Gas Generation 
 EN 60754-2 Acid Gas Generation 
 EN 60332-1 Flame Behavior 
 EN 60332-2 Flame Behavior 
4) CE:EU Low Voltage Directive 2014/35/EC
1) CE: EU Directive 2011/65/EU(RoHS2):
 This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011and the amending Directive 2015/863/EU of 4 June 2015 . No Exemptions are required for RoHS Compliance on this item. Consult Alpha Wire's web site for RoHS C of C.
2) REACH Regulation (EC 1907/2006):
 This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration.
Physical & Mechanical Properties
1) Temperature Range-50 to 90°C(static), -40 to 80°C (dynamic)
2) Bend Radius 4X Cable Diameter(static), 6X Cable Diameter(dynamic)
3) Pull Tension 11.8 Lbs, Maximum
4) Sunlight Resistance Yes
Electrical Properties(For Engineering purposes only)
1) Voltage Rating 600 VRMS
2) Capacitance 17 pF/ft @1 kHz, Nominal Conductor to Conductor
3) Characteristic Impedance89 Ω
4) Inductance0.17 µH/ft, Nominal
5) Conductor DCR15.3 Ω/1000ft @20°C, Nominal
PackagingFlange x Traverse x Barrel (inches)
a) 100 FT 6.5 x 2 x 1.9 Continuous length
b) Bulk(Made-to-order) 
 [Spool dimensions may vary slightly]

Get the abrasion, UV, and oil resistance of a tough zero-halogen Polyurethane jacket in a flex cable that’s up to 40% smaller and 44% lighter than other 600V continuous flex cables.

  • Zero Halogen, contains no heavy metals or phthalates
  • PUR jacket, mPPE insulation
  • 8M+ flex life cycles
  • finely stranded tinned copper conductors, class 6
  • Up to 40% smaller and 44% lighter than standard 600V PUR continuous flex cables
  • UL Oil Res I
  • UL Sunlight Resistant
  • Operating temperature -50C to +90C (static) and -40C to +80C (dynamic)
  • Bend Radius 4X (static) and 6X (dynamic)

With its rugged PUR jacket and finely stranded conductors, EcoFlex PUR cable provides 8+ million flex cycles in tough application conditions—while saving space and reducing weight. And with a wide range of conductor sizes, conductor counts, and shielded and unshielded versions, you can find the cable you need. 

Request a Sample Download Brochure Consult a Cable Expert

Need a more unique construction? Different color code? Different color Jacket?

Request a Custom Quote Resources
AlphaWire