Part # Type  Shielding  Voltage  AWG  # of Elements  Jacket Diameter  Applicable Specifications 
35060 Conductor  UNSHIELDED  300  20  10  0.347  CA Prop 65 
(Ctrl+Click if PDF doesn't appear)
 Diameters (In)
1) Component 1 10 X 1 COND 
a) Conductor 20 (7/28) AWG Tinned Copper 0.038
b) Insulation 0.016" Wall, Nom. PVC 0.070
(1) Color Code Alpha Wire Color Code D
Cond Color Cond Color Cond Color
1 BLACK 5 ORANGE9 VIOLET
2 RED 6 BLUE10 SLATE
3 WHITE 7 BROWN 
4 GREEN 8 YELLOW 
2) Cable Assembly 10 Components Cabled 
a) Twists: 3.0 Twists/foot (min) 
b) Orientation: Components to be arranged from INSIDE LAYER to OUTSIDE LAYER 
c) Core Wrap Clear Mylar Tape, 25% Overlap, Min. 
3) Jacket 0.032" Wall, Nom.,Polyethylene (PE)0.347 (0.362 Max.)
a) Color(s) Slate, Black, Yellow, Orange, Blue, Green, Red, Sand Beige, White
b) Ripcord 1 End 810 Denier Nylon 
c) Print ALPHA WIRE-* P/N 35060 10C 20 AWG
XTRAGUARD(R) 3 80C 300 VOLTS CE ROHS
(SEQ FOOTAGE)
* = Factory Code
1) CE:EU Low Voltage Directive 2014/35/EC
1) CE: EU Directive 2011/65/EU(RoHS2):
 This product complies with European Directive 2011/65/EU (RoHS Directive) of the European Parliament and of the Council of 8 June 2011and the amending Directive 2015/863/EU of 4 June 2015 . No Exemptions are required for RoHS Compliance on this item. Consult Alpha Wire's web site for RoHS C of C.
2) REACH Regulation (EC 1907/2006):
 This product does not contain Substances of Very High Concern (SVHC) listed on the European Union's REACH candidate list in excess of 0.1% mass of the item. For up-to-date information, please see Alpha's REACH SVHC Declaration.
3) California Proposition 65:Exempt from warning labels based on the Consent Judgment. Please see Alpha's CA Prop 65 Statement for more information.
Physical & Mechanical Properties
1) Temperature Range-30 to 80°C
2) Bend Radius 10X Cable Diameter
3) Pull Tension 87 Lbs, Maximum
4) Sunlight Resistance Yes
5) Direct Burial Yes
Electrical Properties(For Engineering purposes only)
1) Voltage Rating 300 VRMS
2) Capacitance 27 pF/ft @1 kHz, Nominal Conductor to Conductor
3) Inductance0.19 µH/ft, Nominal
4) Conductor DCR10.2 Ω/1000ft @20°C, Nominal
PackagingFlange x Traverse x Barrel (inches)
a) Bulk(Made-to-order) 

Xtra-Guard® 3 - Direct burial—no conduit needed Ultraviolet LightOil, Chemicals, Solvents, FuelsDirect BurialEMI Noise

  • The preferred outdoor cable for direct burial
  • 6 times the water resistance of PVC
  • Features a specially formulated polyethylene jacket for outstanding service life and ultraviolet light stability in all jacket colors
  • Resistant to the effects of weathering, moisture, and UV aging without the costly use of conduit
  • Supra-Shield® provides exceptional protection against conducted or electrical noise in high- and low- frequency environments where EMI interference is pervasive